What ventilation do I need?

Part F: what ventilation do I need?

A quick reference for Approved Document F, Volume 1 (2021 edition). A dwelling needs both of the below — worked out independently.

Supply — whole dwelling

Continuous background ventilation, sized for the dwelling as a whole — including make-up air for wet room extract.

→ Section 1
+
both
required
Extract — wet rooms only

Continuous mechanical extract in each kitchen, bathroom, utility and WC — sized on its own, isolated from the supply figure.

→ Section 2

1. Whole-dwelling supply

Continuous supply air, sized for the whole dwelling. Supply units (FLUXO / AUREN) are installed in habitable rooms — bedrooms, living rooms.

Step 1 — work out the target. Use whichever number below is higher.

Bedrooms in dwellingWhole-dwelling rate
1 bed19 L/s
2 bed25 L/s
3 bed31 L/s
4 bed37 L/s
5 bed43 L/s

Or work it out this way: total internal floor area (m²) × 0.3 L/s.

Whichever of the two figures is bigger is the target you design to.

Step 2 — choose units and work out how many

UnitMax outputNotes
FLUXO 1008 L/sBasic, wall switch
FLUXO 15017 L/sBasic, wall switch
AUREN 16017 L/sQuieter, remote control, filtration options

Number of units = target L/s ÷ unit output, rounded up.

Step 3 — position and spread

Install units as high as practically possible. Keep them no more than 400mm below the ceiling, and leave room to reach them for maintenance.

Spread units across the habitable rooms. One per bedroom or living room is typical best practice — though Part F doesn't require it.

Try it yourself — calculate your dwelling

VENTI · Part F quick reference — calculator
Size your dwelling
Approved Document F, Volume 1 (2021 edition) · enter your own numbers below
i
Enter your two numbers
Bedrooms
Total floor area (m²)
1
Step 1 — work out the target (take the higher figure)
Higher — use this
Whole-dwelling rate
Look up bedroom count in the table.
31 L/s
vs
Higher — use this
Floor-area rate
Total floor area (m²) × 0.3 L/s
42 L/s
2
Step 2 — choose a unit and work out how many
42Target L/s
÷
17Unit output
=
2.5Raw result
3Rounded up
Units are always rounded up — a fractional unit can’t be installed, and the design must never fall short of the target.
3
Step 3 — check it clears the target
✓  3 units × 17 L/s = 51 L/s — exceeds the 42 L/s target
Specification for this dwelling
3 × FLUXO 150 / AUREN 160, spread across the habitable rooms — typically one per bedroom or living room.
3Units

2. Wet room extract

A separate requirement, on top of Section 1 — kitchen, bathroom, en-suite, utility and WC each need their own continuous mechanical extract.

Room typeRequired rate (continuous)VENTI unit
Kitchen13 L/sARIA 100 or 150
Bathroom8 L/sARIA 100
Utility room8 L/sARIA 100
WC only (no bath/shower)6 L/sARIA 100

Fit one unit per wet room. Note: ADF(1) doesn't have a separate “en-suite” category — treat an en-suite as a bathroom.

0